LTI Power Systems 10 to 300kva ProUPS
| INPUT |
|
Voltage:
|
3 phase, 3 wire plus ground
|
|
Range:
|
+10%, -20%
|
|
Regulation:
|
+/-1% from 0 to 100% load
|
|
Power Factor:
|
.99 P.F. at full rated load
|
|
Walk-In:
|
10 seconds to full load
|
|
Input THD:
|
Typically Less Than 10%
|
|
Frequency:
|
50Hz or 60Hz +/-6%
|
|
Surge Protection:
|
ANSI C62.41
|
 |
|
|
 |
| OUTPUT |
|
Voltage:
|
3 Phase, 3 or 4 wire plus ground
|
|
Regulation:
|
+/-2% from 0 to 100% load
|
|
Unbalanced:
|
+/-3% for 100% unbalanced load
|
|
Output THD:
|
< 3% linear, < 5% nonlinear load
|
|
Overload:
|
120% for 15 minutes, 150% for 1 minute, bypass 1000% for
1 second
|
|
Slew Rate:
|
1Hz per second (adjustable)
|
|
Frequency:
|
+/-0.01% free running
|
|
| AC Input |
10kva |
15kva |
20kva |
25kva |
30kva |
40kva |
|
Input Voltages (3PH)
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
|
Normal Current Amps
|
31.1
|
13.5
|
46.7
|
20.2
|
62.3
|
27.0
|
77.8
|
33.7
|
93.4
|
40.5
|
124.5
|
53.9
|
|
Max. Current Amps
|
33.3
|
14.4
|
50.0
|
21.6
|
66.7
|
28.9
|
83.4
|
36.1
|
100.0
|
43.3
|
133.4
|
57.8
|
|
Input Distortion
|
< 10% Total Harmonic Distortion at full rated load
|
|
Input Power Factor
|
Typically 1.0 P. F. @ full load
|
|
Input Frequency
|
50/60Hz +/- 6%
|
| AC Output |
10kva |
15kva |
20kva |
25kva |
30kva |
40kva |
|
Output Voltages (VAC)
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
|
Frequency (Hz)
|
60Hz
|
60Hz
|
60Hz
|
60Hz
|
60Hz
|
60Hz
|
|
Full Load (Amps)
|
28.7
|
12.0
|
41.7
|
18.1
|
55.6
|
24.1
|
69.5
|
30.1
|
83.4
|
36.1
|
111.2
|
48.2
|
| DC Link |
10kva |
15kva |
20kva |
25kva |
30kva |
40kva |
|
VDC Nominal
|
360
|
360
|
360
|
360
|
360
|
360
|
|
DC Watts (Full Load)
|
8,800
|
13,200
|
17,600
|
22,000
|
26,400
|
35,200
|
|
DC Amps (Full Load)
|
21.7
|
32.6
|
43.5
|
54.3
|
65.2
|
86.9
|
|
Max. DC Amps
|
27.9
|
41.9
|
55.9
|
69.8
|
83.8
|
111.7
|
|
End of Discharge
|
315 VDC
|
315 VDC
|
315 VDC
|
315 VDC
|
315 VDC
|
315 VDC
|
|
Number of Cells
|
180
|
180
|
180
|
180
|
180
|
180
|
|
VDC Flt./Eq. Range
|
400 to 430
|
400 to 430
|
400 to 430
|
400 to 430
|
400 to 430
|
400 to 430
|
| Efficiency |
10kva |
15kva |
20kva |
25kva |
30kva |
40kva |
|
AC to AC (%)
|
88
|
88
|
88
|
88
|
88
|
88
|
|
DC to AC (%)
|
92
|
92
|
92
|
92
|
92
|
92
|
|
BTU/Hr.
|
3,275
|
4,913
|
6,551
|
8,188
|
9,826
|
13,102
|
| Mechanical |
10kva |
15kva |
20kva |
25kva |
30kva |
40kva |
|
Size W x D x H
|
31.5"x29.5"x65"
|
31.5"x29.5"x65"
|
31.5"x29.5"x65"
|
31.5"x29.5"x65"
|
31.5"x29.5"x65"
|
31.5"x29.5"x65"
|
|
Weight (lbs.)
|
860
|
950
|
1,058
|
1,058
|
1,150
|
1,220
|
| |
 |
|
| ENVIRONMENTAL |
|
Ambient Temperature:
|
0ēC to 40ēC
|
|
Relative Humidity:
|
Up to 95% noncondensing
|
|
Acoustical Noise:
|
65dB 'A' scale at 1 meter
|
|
Altitude:
|
5,000 ft. without derating
|
|
Storage Temperature:
|
-20ēC to 70ēC
|
 |
|
|
 |
| GENERAL INFORMATION |
|
Cable Entry:
|
Top or Bottom
|
|
Ventilation:
|
Forced Air N+1
|
|
Paint:
|
Light Gray
|
|
Cabinet:
|
Seismic Zone 4 Rated
|
|
| AC Input |
50kva |
60kva |
80kva |
100kva |
120kva |
|
Input Voltages (3PH)
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
|
Normal Current Amps
|
155.6
|
67.4
|
186.75
|
80.9
|
248.9
|
107.9
|
311.25
|
134.9
|
373.5
|
161.8
|
|
Max. Current Amps
|
166.7
|
72.2
|
200.1
|
86.7
|
266.79
|
115.6
|
333.48
|
144.5
|
400.1
|
173.4
|
|
Input Distortion
|
< 10% Total Harmonic Distortion at full rated load
|
|
Input Power Factor
|
Typically 1.0 P. F. @ full load
|
|
Input Frequency
|
50/60Hz +/- 6%
|
| AC Output |
50kva |
60kva |
80kva |
100kva |
120kva |
|
Output Voltages (VAC)
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
208
|
480
|
|
Frequency (Hz)
|
60Hz
|
60Hz
|
60Hz
|
60Hz
|
60Hz
|
|
Full Load (Amps)
|
139
|
60.2
|
166.8
|
72.3
|
222.3
|
96.3
|
277.9
|
120.4
|
333.5
|
144.5
|
| DC Link |
50kva |
60kva |
80kva |
100kva |
120kva |
|
VDC Nominal
|
360
|
360
|
360
|
360
|
360
|
|
DC Watts (Full Load)
|
44,000
|
52,800
|
70,400
|
88,000
|
105,300
|
|
DC Amps (Full Load)
|
108.6
|
130.4
|
173.8
|
217.3
|
267.7
|
|
Max. DC Amps
|
139.7
|
167.6
|
223.5
|
279.4
|
335.2
|
|
End of Discharge
|
315 VDC
|
315 VDC
|
315 VDC
|
315 VDC
|
315 VDC
|
|
Number of Cells
|
180
|
180
|
180
|
180
|
180
|
|
VDC Flt./Eq. Range
|
400 to 430
|
400 to 430
|
400 to 430
|
400 to 430
|
400 to 430
|
| Efficiency |
50kva |
60kva |
80kva |
100kva |
120kva |
|
AC to AC (%)
|
88
|
88
|
88
|
88
|
88
|
|
DC to AC (%)
|
92
|
92
|
92
|
92
|
92
|
|
BTU/Hr.
|
16,378
|
19,653
|
26,204
|
32,755
|
39,306
|
| Mechanical |
50kva |
60kva |
80kva |
100kva |
120kva |
|
Size W x D x H
|
49.5"x29.5"x65"
|
49.5"x29.5"x65"
|
49.5"x29.5"x65"
|
49.5"x29.5"x65"
|
49.5"x29.5"x65"
|
|
Weight (lbs.)
|
1,720
|
1,840
|
1,985
|
2,300
|
2,825
|
 |
|
|
Note:
|
- Specifications shown reflect standard 60Hz
UPS models. Models of 50Hz, 400Hz, and single phase or other
input and output voltage configurations are available by contacting
the factory.
- All models are available as stand alone
DC to AC inverters and frequency converters.
- Input or output voltages below 480VAC will
increase the width of the cabinet by 18 inches on models from
100kva to 150kva.
- The rectifier input isolation transformer
option will increase the width 18 inches on all models from
25kva to 100kva and 31.5 inches on all models 120kva and above.
- All data is subject to change without notice.
|
| AC Input |
150kva |
200kva |
250kva |
300kva |
|
Input Voltages (3PH)
|
208
|
480
|
N/A
|
480
|
N/A
|
480
|
N/A
|
480
|
|
Normal Current Amps
|
466.9
|
202.3
|
N/A
|
269.7
|
N/A
|
337.2
|
N/A
|
433.5
|
|
Max. Current Amps
|
500.2
|
216.7
|
N/A
|
289.53
|
N/A
|
361.27
|
N/A
|
433.5
|
|
Input Distortion
|
< 10% Total Harmonic Distortion at full rated load
|
|
Input Power Factor
|
Typically 1.0 P. F. @ full load
|
|
Input Frequency
|
50/60Hz +/- 6%
|
| AC Output |
150kva |
200kva |
250kva |
300kva |
|
Output Voltages (VAC)
|
208
|
480
|
N/A
|
480
|
N/A
|
480
|
N/A
|
480
|
|
Frequency (Hz)
|
60Hz
|
60Hz
|
60Hz
|
60Hz
|
|
Full Load (Amps)
|
416.9
|
180.6
|
N/A
|
240.8
|
N/A
|
301.1
|
N/A
|
361.3
|
| DC Link |
150kva |
200kva |
250kva |
300kva |
|
VDC Nominal
|
360
|
480
|
480
|
480
|
|
DC Watts (Full Load)
|
132,000
|
176,000
|
220,000
|
264,000
|
|
DC Amps (Full Load)
|
325.9
|
325.9
|
407.4
|
488.9
|
|
Max. DC Amps
|
419.0
|
419.0
|
523.8
|
628.6
|
|
End of Discharge
|
315 VDC
|
420 VDC
|
420 VDC
|
420 VDC
|
|
Number of Cells
|
180
|
240
|
240
|
240
|
|
VDC Flt./Eq. Range
|
400 to 430
|
530 to 600
|
530 to 600
|
530 to 600
|
| Efficiency |
150kva |
200kva |
250kva |
300kva |
|
AC to AC (%)
|
88
|
88
|
88
|
88
|
|
DC to AC (%)
|
92
|
92
|
92
|
92
|
|
BTU/Hr.
|
49,132
|
65,510
|
81,888
|
98,265
|
| Mechanical |
150kva |
200kva |
250kva |
300kva |
|
Size W x D x H
|
81"x30"x65"
|
81"x30"x65"
|
81"x30"x65"
|
81"x30"x65"
|
|
Weight (lbs.)
|
2,950
|
3,925
|
4,550
|
4,860
|

One Line Diagram
Note: All data is subject to change without notice.