LTI Power Systems DC to AC Inverters

Model 1kva 2kva 2.5kva 3kva 5kva 7.5kva 10kva
DC Input  
Nominal Voltage (DC) 24 24 48 24 48 120 48 120 48 120 120 48 128
Current (Amps) 46 92 46 114 57 23 69 28 115 46 69 230 92
Noise Feedback Less than 32dBrnC
Protection (Circuit Breaker) 60 100/60 160/80/32 80/32 160/50 80 250 125
AC Output  
Power Rating 1kva
1kw
2kva
1.6kw
2.5kva
2kw
3kva
2.4kw
5kva
4kw
7.5kva
6kw
10kva
8kw
Nominal Voltage 120vac Standard, 100/120/127/200/208/220/230/240 Optimal
Frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz
Frequency Stability ±.01% Internal Crystal Control
Acceptable Bypass Synchronization Standard 58.8Hz to 61.2Hz
Regulation ±2% over entire input voltage and load range
Waveform Sinusoidal
Crest Factor 5:1
Harmonic Distortion Less than 1% with linear load from .8 leading to .8 lagging power factor
Overload 125% for 10 minutes and 150% for 60 seconds
Protection Circuit Breaker
AC Bypass Input  
Voltage 120vac Standard other voltages are available as an option
Frequency 50/60Hz (bypass frequency must match the output frequency)
Environmental  
Operating Temperature 32°F to 122°F (0°C to 50°C)
Cooling Forced Air (front to back)
Heat Dissipation 512
BTU/Hr.
1,024
BTU/Hr.
1,280
BTU/Hr.
1,535
BTU/Hr.
2,559
BTU/Hr.
3,839
BTU/Hr.
5,118
BTU/Hr.
Humidity 0 to 95% non-condensing
Audible Noise Less than 50dB(A) Scale @ 1 meter
Altitude (operating) 5,000 ft. (1,500m)
Dimensions 1kva 2kva 2.5kva 3kva 5kva 7.5kva 10kva
Height (inches) 15.75" 15.75" 15.75" 15.75"/34" 15.75"/34" 34" 34"
Width (inches) 17" 17" 17" 17" 17" 17" 17"
Depth (inches) 15" 15" 15" 15" 15" 15" 20"
Weight (lbs.) 120 130 130 135 150 420 500
Enclosure  
Color ANSI 61 Gray
Rating NEMI 1
Note: All data is subject to change without notice.

Return to LTI Power Systems DC to AC Inverters page

We maintain a fully stocked warehouse, providing our customers the fastest delivery possible.
If your needs are accurate and realistic battery power protection, call the Power Professionals at Battery Electric First.